Overview of indoor vacuum circuit breaker(vcb breaker):
Application: in 40.5kV power distribution system for control and protection.
Standards: IEC 62271-100
Parameters: Rated voltage: 40.5kV.
Rated current: 630-2000A.
Rated short-circuit breaking current: 20-31.5kA.
Features: 1.High insulation level and breaking capacity.
2.Compact and modular deign.
3.Less maintenance.
4.High operation endurance.
5.Applicable to various working conditions
Type and interpretation:
ZN85-40.5/T 口-口
Z ----Vacuum circuit breaker
N ----Indoor
85 ----Design number
40.5 ----Rated voltage(kV)
T ----Spring operating mechanism
口 ----Rated current(A)
口 ----Rated short-circuit breaking current (kA)
Working Condition of vcb breaker:
Ambient air temperature: +15~+40°C
Altitudes:≤1000m
No operating in such places as subject to dust,smog,corrosive/flammable gas,vapor and salt pollution.
Humidity: Daily average value ≤95%
Monthly average value ≤90%
Water vapor pressure: Daily average value ≤2.2kPa
Monthly average value ≤1.8kPa
The external shocking and earthquake could be neglected.
The amplitude of electromagnetic interference in the secondary system ≤1.6kV.
Note:
Customized products for other special working conditions are available on your requirements.
We have developed products suitbable for high altitude.
Main Techincal Parameters of indoor vacuum circuit breaker(vcb breaker):
Item | Technical parameter | ||
Rated volate(kV) | 40.5 | ||
Rated Frequency | 50 | ||
Rated insulation level | Peak rated lightning impulse withstand voltage (kV) | 185 | |
1min power frequency withstand voltage (kV) | 95 | ||
Rated short circuit breaking current (kA) | 20.25 | 31.5 | |
Rated current(A) | 630.1250 | 1250.1600.2000.2500.3150 | |
Rated short circuit closing current (peak kA) | 50.60 | 80 | |
Rated short circuit duration (S) | 4 | 4 | |
Number of starts of rated short circuit current | 30 | 20 | |
Rated operating sequence | 0-0.3S-CO-180S-CO | ||
Mechanical life(times) | 10000 | 10000 |
Drawing: