+86 135 6623 2060 / +86 151 5777 5432
  • Prefabricated Substation
  • Prefabricated Substation

Prefabricated Substation

YB27 series 12KV, 50Hz prefabricated substation (referred to as substation), is used as a substation, power distribution metering, compensation, control and protection device in10KV ring network power, dual power supply or terminal power supply system.
  • Product Description
  • Overview

    1.Rating: Rated voltage : HV equipment10KV and 12KV, LV equipment 0.4 KV.Rated current :HV equipment 630A, LV equipment 1500A.

    2.Application: YB27 series substation is American type combined substation withfunction of high voltage control,

     protect, power transformation and distribution.Usually used in urban and rural power distribution system .

    The high voltage loadswitch and high voltage fuse of this product are installed in the oil of thetransformer,

     with the two structure: in same case with the transformer and indifferent case with transformer. 

    It can be used in high-rise buildings, building inurban and rural areas, residential communities ,high-tech development areas,

    small and medium size factories, mining areas, oil fields, temporary constructionsites, and other premises.

    3.Standard: IEC1330

    Working Conditons

    1.Ambient air temperature: -30℃~+40℃

    2.Altitude: ≤1000m

    3.Wind speed:34m/s ≤700pa

    4.Relative humidity: Daily average relative humidity≤95%.Monthly average relative humidity≤95%.

    5.Installation inclination:≤grade 8 .

    6.Applicable in the places without corrosive and flammable gas.

    Note: Customized products are available.


    PRODUCT SIZE DESCRIPTI

    3

    Main technical parameters


    ItemUnitH.V electrical equipmentTransformerL.V electrical equipment
    Rated voltagekV1010/0.40.4
    Rated currentA630
    100-2500
    Rated frequencyHz505050
    Rated capacitykVA
    100-1250
    Rated thermal stability currentkA20/4S
    30/1S
    Rated dynamic stability
    current (peak)
    kA50
    63
    Rated closing short-circuit
    current (peak)
    kA50
    15-30
    Rated breaking short circuit currentkA31.5 (Fuse)

    Rated breaking load currentA630

    1 min power frequency
    withstand voltage
    kVBetween phases,
    to earth 42,
    to open contacts 48
    35/28(5min)20/2.5
    Lightning impulse withstand voltagekVBetween phases,
    to earth 75,
    to open contacts 85
    75
    Shell protection class
    IP23IP23IP23
    Noise leveldB630Oil transfo rmer<55 Dry transformer<65
    Loops No.

    24~30
    Low voltage side max static var compe nsatorkvar


    300