  • Outdoor Vacuum Circuit Breaker auto recloser
  • Outdoor Vacuum Circuit Breaker auto recloser

Outdoor Vacuum Circuit Breaker auto recloser

ZW32・12〜24KV type outdoor vacuum circuit breaker (high voltage VCB,also well known as Auto recloser.
Which is suitable for the 3 phase power system with AC 50Hz,volttage 10-12 KV
The ZW32-12 outdoor high-voltage AC vacuum circuit breaker complies with GB1984-2014 "AC High-Voltage Circuit Breakers" and the relevant IEC standards."
  • Product Description
  • ZW32・12〜24KV Overview

    ZW32-12 outdoor high voltage vacuum circuit breaker(hereinafer referred to as circuit breaker) is rated voltage of 12kv, 

    50hz three-phase AC outdoor power distribution equipment.Mainly used for breaking, closing load current, 

    overload current and mining enterprise in the distribution system to do protection and control,

    especially for rural power grids and the place for frequent operations.


    ZW32-12-24KV outline and mounting dimensions:

    drawing.jpg


    Reference standards:

    GB/T 1984 "High voltage AC circuit breaker"

    GB/T11022 "High voltage switchgear and control equipment standard common technical requirements"

    GB/T311.1 "Insulation coordination of high voltage power transmission equipment: high pressure test technology"

    DL/T 403" 12-40.5kV high voltage vacuum circuit breaker ordering technical conditions"


    Environmetal conditions for usage:

    Altitude does not exceed 1000m

    Ambient air temperature:-40℃~+40℃

    Wind speed is not greater than 35m/s.

    Pollution level:Class IV

    Installation site:no flammable, no explosive hazard,no chemical corrosion.

    Earthquake intensity does not exceed 8 degrees.


    Main features:

    Vacuum Circuit breaker adopts three-phase pillar structure, it has reliable breaking performance,

    no combustion and explosion hazard, maintenance-free,small size, light weight and long service life etc.


    Vacuum circuit breaker with a fully enclosed structure, good sealing performance,

    help to improve the moisture,anti-condensation performance,especially adapted to the use of cold or wet areas.


    Three-phase pillars and current transformer using imported outdoor epoxy resin solid insulation,

    which has high and low temperature resistance,resistance to ultraviolet light, andti-aging characteristics.


    Operatiing mechanism using small spring operating mechanism, low energy consumption for breaking-closing; 

    use of direct transmission mode, sub-closing parts less,high reliablility.The operating mechanism and

     the arc extinguishing system are placed in a sealed mechanism box to solve the problem of corrosion of components

     such as parts and improve the reliablility of the circuit breaker.


    Vacuum circuit breaker sub-closing operation can be used manual or electric operation and remote operation.

    It can be equipped with the controller to achieve power distribution automation,it can also be combined with 

    the control of the recloser automatic recloser.


    The vacuum circuit breaker can be equipped with two-phase or three-phase CT for over-current automatic trip protection

     and intelligent controller for information analysis.


    The total mass of the circuit breaker (without isolation switch) 105KG,(with disconnector) 125KG.


    The main technical parameters:

    No.ItemUnitValue
    1Rated voltagekV12
    2Rated frequencyHz50
    3Rated currentA630,1250,
    4

    Rated short-circui

    t breaking current

    kA16,20,25
    5Rated peak withstand current40,50,63
    6

    Rated short-tim

    e withstand current

    16,20,25
    7Rated short-duration currentS4
    8

    Rated short circui

    t closing current(peak)


    40,50,63
    9Rated operation sequencetime
    O_0.3S_180S_CO
    10mechanical life1000/isolating switch 2000
    11

    Rated curren

    t breaking times

    10000
    12

    Rated short circui

    breaking current breaking times

    50
    13

    Power frequency

     withstand voltage

    (1min

    (wet)alternate to

     the ground

    (dry) interphase,

    ground/fracture

    KV

    34

    42/48

    14

    Lightning impulse

     withstand voltage(peak)


    interphase,ground/fracture

    75/85
    15

    Secondary circuit

     1min power frequency 

    withstand voltage 

    (expect electronics)

    V2000