Outdoor Disconnecting Switch

GW5 Use environmental conditions
GW5-40.5 outdoor disconnecting switch
Stamdard: IEC60129
  • Product Description
  • Overview:

    GW5-40.5 outdoor isolation switch for AC 50Hz outdoor high voltage electrical equipment, rated voltage level of 40.5kV, 

    for high voltage lines in

     ● each isolation switch single pole by two pillar insulators, respectively fixed on a base, 

    the intersection Angle of 50° to form a V-shaped structure, mainly by

    Open and close without load, and electrical isolation of high-voltage lines of electrical equipment such as 

    high-voltage bus and circuit breaker under maintenance: base part, pillar insulator, connection seat part, contact head part, grounding knife, 

    grounding static contact, terminal, etc.

    It can also be used to open and close small capacitive or inductive currents. 

    ● The isolation switch is divided into three types: ungrounded, 

    single grounded and double grounded. There is a mechanical interlock between the main shaft and the grounding knife, and an auxiliary switch. open

    This series of outdoor isolators meet GB1985 "AC high voltage isolator and Ground switch", 

    IEC60129 "AC isolator and switch switch operation mode has manual and electric two.

    Ground switch "and GB/T11022" Common Technical Requirements for high voltage switchgear and control equipment standards "and other standards.


    Technical Parameter of disconnecting switch:

    ItemUnitData
    Rated voltageKV40.5

    Rated insulation

    level

    1min power frequency 

    withstand voltage

    (to earth/fracture)

    KV95/115

    Rated lighting impulse

    withstand voltage

    (peak) (to earth/fracture)

    kV185/215
    Rated frequencyHZ50
    Rated currentA630,1250,1600,2000
    Rated short time withstand currentKA20,31.5,40
    Rated peak withstand currentKA50,80,100
    Rated short circuit duration(main switch/earth switch)S4/2
    Rated terminal mechnical loadHorizontal longitudinal loadN750

    Horizontal lateral loadN500

    Vertical forceN750
    Creepage distance
    mm1013-1256
    Mechanical life

    times2000
    Manual operatiing mechanismwithout earthing
    CS17,CS17G

    Control circuit voltageVAC220,DC110,DC220
     Motorized operating mechanismModel
    CJ6

    Motor voltageVAC380

    Control circuit voltageVAC220,AC380,DC220

    Closing/opening timeS6±1


    structural features of disconnecting switch:

    ● Each isolation switch single pole by two pillar insulators, respectively fixed on a base, 

    the intersection Angle of 50° to form a V-shaped structure, mainly by

    Open and close without load, and electrical isolation of high-voltage lines of electrical equipment such as

     high-voltage bus and circuit breaker under maintenance: base part, pillar insulator, connection seat part, 

    contact head part, grounding knife, grounding static contact, terminal, etc.

    It can also be used to open and close small capacitive or inductive currents.


    ● The isolation switch is divided into three types: ungrounded, single grounded and double grounded.

     There is a mechanical interlock between the main shaft and the grounding knife, and an auxiliary switch. open

    This series of outdoor isolators meet GB1985 "AC high voltage isolator and Ground switch", 

    IEC60129 "AC isolator and switch switch operation mode has manual and electric two.

    Ground switch "and GB/T11022" Common Technical Requirements for high voltage switchgear and 

    control equipment standards "and other standards. 


    This disconnecting switch has the following characteristics:

    1, flexible rotation, open and close freely. Due to the use of rolling bearing transmission, 

    so in the process of rotation is more flexible, more labor-saving operation.

    2, through the bevel gear mechanism to drive, so as to ensure that the two columns of the closing action is consistent.

    3. Divide and close the limited position device to ensure that the contact is in the best position.

    At the same time, the handle is locked by the lock ring after the operation, so as not to occur

    Under the action of the external force of consciousness, the reliability of the position is guaranteed.

    4, contact distance is large, there is enough margin of insulation isolation fracture, so as to ensure its safety.

    5, there are three ways of grounding and ungrounding,

     there is a reliable mechanical interlock between the spindle and grounding, so as to ensure safety, users can according to the need

    G W 5 - (40.5) D

    Choose the grounding mode.

    6, according to the user's convenience, the operation mechanism can be installed below any pole, the operation effect is the same.