+86 139 6879 9444 / +86 151 5777 5432
  • High Voltage Switchgear
  • High Voltage Switchgear

High Voltage Switchgear

KYN61-40.5(Z) type alternating-current metal-clad and metal-enclosed withdrawable switchgear is a indoor complete set of power distribution unit of three-phase AC50Hz and rated voltage of 40.5kV.
Standard:GB/ T11022-1999, GB3906-1991, DL404-1997,etc
  • Product Description
  • Overview

    KYN61-40.5(Z) type alternating-current metal-clad and metal-enclosed withdrawable switchgear

     (hereinafter referred to as switch gear)---high voltage switchgear is a indoor complete set of power distribution unit of 

    three-phase AC50Hz and rated voltage of 40.5kV. Used for receiving and distributing the electric energy in power plants, 

    transformer substations,mining and industrial enterprises, etc.,

     it controls, protects and detects the circuits, also is applicable to frequent operation locations. 

    This switchgear complies with GB/ T11022-1999, GB3906-1991, DL404-1997,etc.

     

     

    High voltage switchgear series

    Main feature

    1. Cabinet structure is of assembly type, the circuit breaker adopts floor type handcart structure;

    2. Equipped with brand new composite insulated vacuum circuit breaker,

     is featured with good interchangeability, and is simple to change;

    3. The handcart frame is mounted with lead screw nut propelling mechanism, it is able to move the handcart easily, 

    and prevent damage of propelling mechanism caused by misoperation;

    4. All operations can be carried out when the cabinet door is closed;

    5. Interlocking among the main switch, handcart and switchgear adopts compulsory mechanical locking mode,

     meeting the "five preventions” function;

    6. Cable chamber is large enough, it could connect multi cables;

    7. The fast earthing switch is used for earthing and circuit short-circuit;

    8. Degree of protection of the enclosure is IP3X, and is IP2X when the door of handcart chamber is opened;

    9. The product complies with GB3906-1991, DL404-1997 and refers to the international standard I EC-298.


    Use environmental conditions

    1. Ambient temperature: -10°C 〜+40°C, mean value measured within 24h should not exceed 35°C .

    2. Altitude: not exceed 1000m;

    3. Relative humidity: daily mean not over 95%, monthly mean not over 90%;

    4. Seismic intensity: not beyond Ms8;

    5. Vapor pressure: daily mean not over 2.2kPa, monthly mean not over 1.8kPa.

    6. Ambient environment: the installation site should be free of fire, explosive danger, serious pollution, 

    chemical corrosion or severe vibration.


    Main technical parameters

     

    Name

    Unit

    value

    Rated voltage

    kV

    40.5

    Rated current

    A

    12501600 2000

    Rated frequency

    Hz

    50

    Rated short-time 

    withstand current

    kA

    20 25 31.5

    Rated peak withstand current

    kA

    50 63 80

    Rated power frequency

     withstand voltage

    kV

    95/lmin

    Rated lightning impulse

     withstand voltage

    kV

    185

    Rated short-circuit duration

    s

    4

    Degree of protection


    IP3X

     

    Main technical parameters

     

    Name

    Unit

    value

    Rated voltage

    kV

    40.5

    Rated frequency

    Hz

    50

    Rated power frequency 

    withstand voltage

    kV

    95/lmin

    Rated lightning impulse

     withstand voltage

    kV

    185

    Rated current

    A

    12501600 2000

    Rated short-time 

    withstand current

    kA

    20 25 31.5

    Rated short-time breaking current

    kA

    20 25 31.5

    Rated peak 

    withstand current

    kA

    50 63 80

    Rated short-circuit duration

    ms

    4

    Opening time

    ms

    30 W t W 60

    Closing time

    s

    50 W t W 100

    Rated short-circuit breaking

     current times

    times

    20

    Mechanical life

    times

    10000

     

    Main technical parameters

     

    Name

    Unit

    value


    Rated operating voltage

    Opening coil

    Closing coil

    V

    DC220/110, AC220/110

    Rated operating current

    Opening coil

    Closing coil

    A

    0.96(220V), 1.05(110V)

    Power of energy-storage motor

    W230

    Rated voltage of

     energy-storage motor

    VDC220/110, AC220/110

    Energy-storage time

    SW 12
  • Website information update...
  • Power transformer Substation series Switchgear series High voltage component Electric meter New energy battery Cable jacket Wire and cable Diesel generator

LEAVE A MESSAGE

LEAVE A MESSAGE
If you are interested in our products and want to know more details,please leave a message here,we will reply you as soon as we can.