  • ZN12-40.5 indoor vacuum circuit breaker
  • ZN12-40.5 indoor vacuum circuit breaker

ZN12-40.5 indoor vacuum circuit breaker

ZN65A-40.5 series indoor AC high voltage vacuum circuit breaker (hereinafter referred to as circuit breaker), suitable for three-phase AC,
50Hz, 40.5kV power grid, as control and protection equipment. As a relatively independent circuit breaker unit, can be used with a variety of form of switch cabinet matching use.
  • Product Description
  • 1.Summarize

    ZN65A-40.5 series indoor AC high voltage vacuum circuit breaker (hereinafter referred to as circuit breaker), suitable for three-phase AC,

    50Hz, 40.5kV power grid, as control and protection equipment. As a relatively independent circuit breaker unit, can be used with a variety of  form of switch cabinet matching use.

    1.1 Environmental Conditions

    The environmental conditions for normal use of circuit breakers are as follows:

    1.1.1 The upper limit of ambient air temperature is +40℃; The lower limit is -25 ° C.

    1.1.2 Elevation below 1000m.

    1.1.3 The daily average relative humidity is not more than 95%, and the monthly average is not more than 90%; Daily mean saturated vapor pressure no

    Greater than 2.2×10-3MPa, the monthly average is not greater than 1.8×10-3MPa.

    1.1.4 No corrosive gas, no frequent violent vibration.

    2.Technical Parameters

    2.1 Model Significance:

    ZN 65A-40.5/口-口

    Z  ------Vacuum circuit breaker

    N  -----Indoor

    65A ----Design Sequence number

    40.5 ----Rated voltage

    口  ----- Rated current

    口  -----Rated short-circuit breaking current


    2.2 Technical Parameters of indoor vacuum circuit breaker:

    SNParameter Name UnitTechnical Spefication
    1Rated voltage
    KV40.5
    2Rated currentA630,1000,1250,1600
    3Rated short-circuit breaking currentkA20
    25

    31.5
    4Dynamic stable current( peak)kA50

    6380
    5Heat stable current(4s)kA202531.5
    6Rated short-circuit  closing current(peak)kA206380
    7Rated short-circuit breaking current breaks timesTimes30

    8

    Rated operation sequence

    Open-0.3s-close open-180s-close  open
    9Rated lightning impulse withstand voltage( full wave)KV

    18S

    10Rated short-time power frequency withstand voltage( 1min)KV95
    11Closing timeS≤0.09
    12Switching timeS≤0.075
    13Mechnical lifeTimes10 000
    14

    Rated current breaking times

    Times

    10 000
    15The energy storage motor rated frequencyW≈275
    16Energy storage mote rated voltageV≈100  200
    17Energy storage timeS≤15
    18Rated voltage of closing electromagnetV-110 220
    19Switch solenoid rated voltageV-110 220
    20The energy storage shunt release rated voltageV≈110 220
    21Closing  interlock rated voltageV≈110 220
    22The no-voltage trip device rated voltageV≈110 220
    23Rated current of the  overcurrent  trip deviceA5
    24Rated current of the auxiliary switchAAC10   DC5


    3. Drawing of vacuum circuit breaker:

    drawing.jpg