+86 139 6879 9444 / +86 151 5777 5432
  • SF6 high voltage insulator switch
  • SF6 high voltage insulator switch

SF6 high voltage insulator switch

FZW-12/24/40.5 outdoor post SF6 insulated load switch--high voltage insulator switch
according IEC60265-1(1988),GB40.504-1990 standard.
  • Product Description
  • Overview:

    Column installed insulation load switch,type FZW-12/24/40.5-20,is suitable for the rated voltage

    12/24/40.5kV,rated current 400A、630A、50/60Hz power grid open circuit、load current inclosed Power system、

    Over load curren.This load switch can separate those broken distribution line automatically.

    With the latest technology,it has the newest electronic controller.The switch can be used by manual operation,

    Electric operation and operation from along distance.Electronic controller is installed in a stainless steel cabinet

    Which is suitable for using under all kinds of climatic conditions.In addition,there are some wired and wireless

    Modem installed in the cabinet through which it can realize the remote monitoring and control.Simple installation

    On column is convenient,fast,and also can reduce the construction cost.

     

    The standard conditions of our SF6 high voltage insulator switch:

    Operating conditions for SF6 gas load switch to adapt to:

    (1) . Ambient air temperature :upper limit+50℃,lower limit of -40℃。

    (2) Relative humidity:100%

    (3) Elevation does not exceed 1000m;2000m;3000m;5000m.

    (4) The pressure does not exceed 700pa( equivalent to wind speed of 34m/s)

    (5) Earthquake intensity:8 degree

    (6) Installation site:No fire,no explosion hazards, no chemical corrosion and recurrent severe vibration.

    (7) Pollution class: classⅢ,classⅣ.

     

    Features of SF6 insulated load switch:

    (1)SF6 gas-insulted

    (2)SF6 gas is a kind of nontoxic, nonflammable and electrical insulating gas.

    It has the excellent characteristic of arc extinction.

     

    Note:Each switch before leaving the factory has been filled with SF6 gas, 

    sealed,and test according IEC60265-1(1988),GB40.504-1990 standard.

     

     

    Parameters ratings of SF6 high voltage insulator switch:

    No.

    Name

    Unit

    Data


    Product mode


    FZW-12

    FZW-24

    FZW-40.5

    1

    Rated voltage

    kV

    12

    24

    40.5

    2

    Rated frequency

    Hz

    6/10/11

    15/17.5/20

    3/36/40.5

    3

    Rated insulation level( the filling SF6 gas 0.07Mpa20℃)

    Lightning impulse withstand voltage)

    relatively

    kV

    75

    125

    185

    Fracture

    85

    145

    215

    Power frequency withstand voltage 1 min

    relatively

    kV

    42

    64

    95

    Fracture

    50

    79

    110

    4

    Insulation level of zero gauge pressure

    Power frequency withstand voltage 1min

    kV

    30



    RP-pressure 1min

    30

    The highest phase voltage 5min

    9

    5

    Rated current

    A

    630(400)

    630(400)

    630(400)

    6

    Rated breaking load current( 0.07Mpa/20℃)

    A

    630(400)

    630(400)

    630(400)

    7

    Breaking current under zero gauge pressure

    A

    630(400)

    630(400)

    630(400)

    8

    Peak withstand current

    kA

    50

    50

    50

    9

    Rated short time making current

    kA

    50

    50

    50

    10

    Rated short time withstand current

    KA/S

    20/4

    20/4

    20/4

    11

    Rated cable charging breaking current

    A

    25

    25

    25

    12

    Rated line charging breaking current

    A

    16

    16

    16

    13

    Rated closed-loop breaking current

    A

    630(400)

    630(400)

    630(400)

    14

    Exciting current

    A

    21

    21

    21

    15

    Rated current breaking times

    Times

    400

     

    400

     

    400

     

    16

    Rated working pressure

    Mpa

    0.05

     

    0.07

     

    0.1

    17

    Per-phase main circuit resistance

    μΩ

     

    150

     

    150

     

    150

     

    18

    Relative gas leakage rate

    year

    1%

     

    1%

     

    1%

     

    19

    SF6 gas moisture content

    Factory transfer of value

    ppm

    150

     

    150

     

    150

     

    Switch running value

    ppm

    300

     

    300

     

    300

     

    20

    Operation of echanical stability

    times

    6000

     

    6000

     

    6000

     

    21

    Rated operating voltage and auxiliary circuits rated voltage

    V

    DC 220/

    110/48/24

     

    DC 220/

    110/48/24

     

    DC 220/

    110/48/24

     

    AC 220/110

    AC 220/110

    AC 220/110

    22

    Weight

    Type M

    kg

    115

    125

    135

    Type A

    135

    145

    155

    23

    Institutions boxes and controlled protection class

    IP44 IP55

    24

    Type of Mounting

    The lifting type( suspended)/block(horizontal)

     

    Size:

    Dimensions(mm)

    Installation dimentions (mm)

    Casing creepage distance(mm)


    A

    B

    C

    Long*Width


    12Kv

    225

    435

    500

    500*125(280)

    540

    24Kv

    300

    435

    500

    500*125(280)

    750

    40.5Kv

    350

    435

    500

    700*125(280)

    1050

     