+86 135 6623 2060 / +86 151 5777 5432
  • high voltage insulator switch
  • high voltage insulator switch

high voltage insulator switch

GW5-126 high voltage insulator switch, 3 phase current 50Hz,for 110KV rated voltage power system.
Elevation not exceed: 2000m
  • Product Description
  • Application:

    GW5-126 high voltage insulator switch is three phase current 50Hz outdoor high voltage current electrical appliances,used for 110kV rated voltage power system, 

    for the high voltage line under the condition of no-load current switching circuit and on the maintenance of electrical equipment such as high voltage bus、

    circuit breaker etc. Electrical equipment and live high voltage wire electrical isolation,provide a visible isolated distance for the inspectors and maintenance staff,

    in order to protect the security of the maintenance staff.

     

    Operating environment condition:

    1. The elevation not exceed: 2000m

    2. Environment temperature: -40℃~+40℃

    3. Maximum windy speed:34m/s

    4. Earthquake resistance ability: level acceleration:0.250g  vertical acceleration: 0.125g

    5. Ice thickness not exceed: 10mm

    6. Insulator pollution level:Ⅲ(25mm/kV)、Ⅳ(31mm/kV)

    7. Installation place free from the  harmful material of flammable,explosive,chemical corrosion,etc,

    should be free of frequent and violent shaking.

     

    Main technology parameter:

    Item



    Unit

    Parameter

    Rated voltage



    kV

    126

    Rated current



    A

    2000

    Rated peak withstand current( peak)



    kA

    100

    3S rated short-time withstand current(effective)



    kA

    40

    Rated frequency



    Hz

    50

    Grounding switch

    Rated peak withstand current( peak)


    kA

    100

    3S rated short-time withstand current( effective)


    kA

    40

    Grounding terminal rated pull


    lengthways

    N

    1000


    widthways

    N

    750



    vertical

    N

    1000

    Rated isolation level

    Rated short-time frequency withstand voltage( effective)

    grounding

    kV

    230

    Open contacts

    kV

    230+70

    Lightning impacting tolerance withstand voltage( effective)

    Grounding

    kV

    550

    Open contacts

    kV

    550+100

    Grounding switch induction current opening and closing ability test

    Electromagnetic coupling

     Rated induction current

    A

    50

    Rated induction current

    kV

    0.5

    Electrostatic coupling

    Rated induction current

    A

    0.4

    Rated induction current

    kV

    3

    Post insulator creep-age distance


    mm/kV

    25


    31

    Mechanic lifetime



    times

    3000

    Insulator switch circuit resistance



    μΩ

    85

    Open and close bus switching current



    A

    1600

    Uni-polar weight




    230

     

    Ordering instruction:

    1. Insulator type、specification、numbers

    2. Rated current、rated short-time and peek withstand current、porcelain bottle pollution-proof level.

    3. Need grounding knife or not, which side, need magnetic lock or not--please remark.

    4. Electrical operating construction’s motor voltage、control voltage、assistant switch poles.

    5. Please kindly remark if there is another special requirements.