Parameters:
12-15kV
Type | Rated voltage (kV) | Rated Current (A) | Breaking Current (A) | Impulse Voltage (kV) | Power-frequency withstand voltage | Creepage Distance (mm) | Weight(kg) | Dimension(cm) |
RW12-12/100 | 12-15 | 100 | 8000 | 110 | 40 | 250 | 5.5 | 41*36*9.5 |
RW12-12/100 | 12-15 | 200 | 10000 | 110 | 40 | 250 | 6 |
20-30kV
Type | Rated Voltage (kV) | Rated Current (A) | Breaking Current (A) | Impulse Voltage (kV) | Power-frequancey Withstand voltage (kV) | Creepage distance (mm) | Weight (kg) | Dimension (cm) |
PW12-30/100 | 20-30 | 100 | 8000 | 170 | 70 | 700 | 10.5 | 59*36*13.5 |
PW12-30/200 | 20-30 | 200 | 10000 | 170 | 70 | 700 | 11.0 |
33-36kV
Type | Rated voltage (kV) | Rated Current (A) | Breaking Current (A) | Impulse Voltage (kV) | Power-frequency withstand voltage (kV) | Creepage distance (mm) | Weight (kg) | Dimensiton (cm) |
-33/100 | 33-36 | 100 | 8000 | 170 | 70 | 720 | 12.5 | 66*37.5*14 |
-33/200 | 33-36 | 200 | 10000 | 170 | 70 | 720 | 13.0 |
12-15kV
Type | Rated voltage (kV) | Rated current (A) | Breaking current (A) | Impulse voltage (kV) | Power-frequency withstand voltage (kV) | Creepage distance (mm) | Weight (kg) | Dimension (cm) |
-12/100 | 12-15 | 100 | 8000 | 110 | 40 | 380 | 3.7 | 41.5*37.5*10.5 |
-12/200 | 12-15 | 200 | 10000 | 110 | 40 | 380 | 4.0 |
20-30kV
Type | Rated voltage (kV) | Rated current (A) | Breaking current (A) | Impulse Voltage (kV) | Power-frequence withstand voltage (kV) | Creepage distance (mm) | Weight (kg) | Dimension (cm) |
-30/100 | 20-30 | 100 | 8000 | 170 | 70 | 670 | 4.3 | 55.5*37.5*12.5 |
-30/200 | 20-30 | 200 | 10000 | 170 | 70 | 670 | 4.5 |
33-36kV
Type | Rated voltage (kV) | Rated current (A) | Breaking current (A) | Impulse voltage (kV) | Power-frequency withstand voltage (kV) | Creepage distance (mm) | Weight (kg) | Dimension (cm) |
-33/100 | 33-36 | 100 | 8000 | 170 | 70 | 740 | 4.4 | 61.5*38*11.5 |
-33/200 | 33-36 | 200 | 10000 | 170 | 70 | 740 | 4.8 |
FAQ:
1.What is a drop out fuse?
Drop Out Fuses are protection devices that protect networks and equipment from current surges and overloads.
An over-current will melt the fuse element in the carrier disconnecting the line or equipment.
They also provide network isolation points when manually operated with a hot stick
2.How does a drop out fuse protect a transformer?
The drop-out fuse can disconnect the power supply when there is a fault inside the 10kv class distribution transformer,
and it is also convenient for the normal operation of the 10kv class distribution transformer.
In addition, the price is cheap, the structure is simple, and the installation is simple.
We are manufacturer and good at wholesale drop out fuse.
Wish can establish good business relationship with the customers in the worldwide.