Profile:
LW36A-126/145 high voltage current SF6 breaker is suitable for the areas which current is 50HZ、126kV,
and the elevation is under 2500meters,used for turning on/off the electricity system, cutting down the under-load current
and the short-circuit fault circuit, controlling 、protecting the power equipment and link circuit.
Breakers uses the SF6 gas( the Alpine region use the gas mixture of SF6 and CF4) as the isolate and arc extinguishing medium,
adopt the theory of automatic arc extinguishing,and match the spring operate instruction,
has the advantages of powerful turn on/off ability and lower frequency, higher reliability...etc.
These products have passed the completely test of government high voltage electrical quality monitor center--
Xian high voltage electrical research institution.
The standards of high voltage SF6 circuit breaker:
IEC62271-100 high voltage current breaker
GB1984 high voltage current breaker
GB/T11022 The shared technology requirements of high voltage switch equipment and control equipment standard
Advantages of high voltage SF6 circuit breaker:
Can be used for the the current system of three phase natural grounded or ungrounded.
Suitable for the alpine region which above is 2500m.
Can work under the lower temperature which is -45℃
Operating environment:
Use normal environment conditions in accordance with the standard GB/T11022
《The shard technology requirements of high voltage switch equipment and control equipment standard》.
1. The around environment temperature: -45℃~+40℃
2. Elevation: not exceed 2500m (126kV); not exceed 1000m(145kV)
3. Wind speed:≯34m/s
4. Daily temperature difference:≯25℃
5. Sunlight strength:≯0.1w/cm
6. Monthly average relative humidity:≯90%
7. Earthquake acceleration:Level ≯0.2g level;Vertical ≯0.1g
8. Ice thickness:≯10mm
9. Pollution level: Ⅲgrades( creepage distance 25mm/kV) or Ⅳgrades( creepage distance 31mm/kV)
10. Installation : outdoor
No. | Item | Unit | Parameters | ||
1 | Rated voltage | 126 | 145 | ||
2 | Rated power frequency withstand voltage (1min) | Over the ground、phases | kV | 230 | 275 |
Between the contacts | 265 | 275 | |||
3 | Rated lightning impulse withstand voltage | Over the ground、phases | 550 | 650 | |
Between the contacts | 630 | 650 | |||
4 | SF6 the power frequency withstand voltage of 0meter | 95 | 105 | ||
5 | Rated frequency | Hz | 50 | 50 | |
6 | Rated current | A | 3150 | 3150 | |
7 | The first coefficient of open pole | 1.5 | 1.5 | ||
8 | Rated short-circuit on/off current | kA | 40 | 40 | |
9 | Rated short-circuit close/open current | 100 | 100 | ||
10 | Rated shore-time withstand current | 40 | 40 | ||
11 | Rated peak withstand current | 100 | 100 | ||
12 | Rated short-circuit continues time | 4 | 4 |