+86 139 6879 9444 / +86 151 5777 5432
  • GCK lv panel
  • GCK lv panel

GCK lv panel

GCK low-voltage extraction switchgear is widely used in power plants, metallurgical steel rolling, petrochemical, light textile, port terminals, buildings, hotels and other places as AC three-phase four
For distribution and centralized control of electric motors in power supply systems with voltage 380V, 660V, frequency 50Hz and rated current 5000A or below.
  • Product Description
  • Brief instruction:

    GCK low-voltage extraction switchgear(GCK lv panel) is widely used in power plants, metallurgical steel rolling, petrochemical, light textile, 

    port terminals, buildings, hotels and other places as AC three-phase four

    For distribution and centralized control of electric motors in power supply systems with voltage 380V, 660V,

     frequency 50Hz and rated current 5000A or below.


    Basic info of lv panel:


    Model No.GCKVoltageAC380V

    Transport

    Package

    CustomizedSpecificationAs per data sheet
    TrademarkEBLOriginChina



    GCK Overview

    GCK LV withdrawable switchgear cabinetis applicable to the low voltage distribution system with AC50Hz, 

    rated working voltage 380V. It contains power center(PC)and motor control center(MCC)functions. 

    Each technical parameter all reaches national standards. With characteristics of advanced structure,

    beautiful appearance,high electric performance, high protect-ion grade, reliable and safe and easy to maintain.

    lt is the ideal distribution device for low voltage power supply system in metallurgy, petroleum,chemical,power, 

    machinery and light weaving industries etc.

    The product accords with standards IEC-439,GB7251.1


    GCK Design feature

    1.GCK1 and REGCJ1 are assemble type combined structure.The basic skeleton is assembled by adopting special bar steel,

    2.Cabinet skeleton,component dimension and starter size change according to basic modulus E=25mm.


    3. In MCC project, parts in cabinet are divided into five zones(compartment):horizontal bus bar zone,

    vertical bus bar zone,function unit zone, cable compartment, and neutral earthing bus bar zone. 


    Each zone is separated mutually for circuit’s normal running and effectively preventing fault expansion.

    4.As all structures of framework are connected and firmed by bolts, 

    so it avoids the welding distortion and stress, and upgrades the precision.


    5. Strong general performance, well applicability and high standardization degree for components.


    6. Draw-out and insert of function unit(drawer) is lever operation,which is easy and reliable with rolling bearing.


    GCK the main technical parameters:

    Protection gradeIP40 IP30
    Rated working voltageAC 380(V)
    Frequency50Hz
    Rated insulation voltage660V
    Working conditions
    EnvironmentIndoors
    Altitude≤ 2000M
    Ambient temperature-5℃~+40℃

    The min temperature 

    under store 

    and transporation

    -30℃
    Relative humidity≤90%
    Capacity of control motor(kW)0.4-155
    Rated current(A)
    Horizontal bus bar1600 2000 3150

    Vertical bus bar

    630 800

    Contact connectors 

    of main circuit

    200 400
    Supply circuit1600
    Max currentPC cabinet630

    Power receiving circuit

    MCC cabinet

    1000 1600 2000

    2500 3150

    Rated short time

    withstand current(kA)


    Virtual value50、80
    Peak value105、176

    Line frequency

    withstand voltage

    (V/1min)

    2500